Analysis of the core content of the standard
As a mandatory national standard, this standard specifies the technical requirements for the entire life cycle of liquefied petroleum gas pressure regulators, with key points including:
- Pressure range: Inlet pressure 0.03-1.56MPa, household rated outlet pressure 2.80kPa
- Environmental adaptability: Working temperature -20℃~+45℃
- Safety classification: Three types of safety devices: overpressure cut-off (C), low pressure cut-off (D), and overcurrent cut-off (L)
Comparison of key technical indicators
Parameters | Household pressure regulator (JYT) | Commercial pressure regulator (SYT) |
Rated flow rate (m³/h) | ≤2.0 | ≤3.6 |
Closing pressure (kPa) | ≤4.00 | ≤6.25 |
Mechanical durability | 50,000 opening and closing tests |
Technical requirements for safety devices
Overpressure cut-off device
The error between the measured cut-off pressure and the set value must be <±15%. Typical case: when the set value is 5kPa, the actual cut-off range should be 4.25-5.75kPa.
Material verification requirements
Key materials must pass a 72-hour corrosion resistance test:
- The mass change rate of rubber parts in n-pentane is ≤±20%
- Plastic parts must not be deformed or cracked in n-hexane
Implementation suggestions
- Selection guide: For commercial scenarios, the SYT series must be selected and marked as "Forbidden for home use"
- Installation specifications: Quick-release connectors must pass 5,000 plug-in and pull-out tests
- Maintenance cycle: It is recommended to replace them within 8 years from the manufacturing date