Heat pump water heaters for commercial or industrial and similar purposes (English Version)
GB/T 21362-2023, as the first revision of the 2008 version of the standard, responds to the demand for energy efficiency improvement under the dual carbon goals. The main technological evolution is reflected in:
Technical dimension | 2008 version | 2023 version | Range of change |
---|---|---|---|
Model classification | 4 categories | Added static heating type | +25% |
Energy efficiency index | COP single point test | AHPF annual comprehensive energy efficiency | Test cycle extended by 300% |
Noise limit | Uniform value | Classification by model | Accuracy improved by 40% |
Standard construction of three-dimensional classification matrix:
Model | COP limit (kW/kW) | AHPF limit | Noise dB(A) |
---|---|---|---|
Static heating type | 2.90-4.20 | 2.40-2.80 | ≤65-78 |
Single heating type | 3.20-4.50 | 2.70-3.10 | ≤63-76 |
Note: Low temperature units need to run continuously for 1h at -25℃ without tripping protection
New dynamic test requirements under defrost conditions, data collection interval ≤5s, must meet the following requirements
Added 8-level load evaluation system for units <10kW:
Grade | V40 water volume (L) | Effective internal energy (kWh) |
---|---|---|
XS | 8-16 | 0.135-0.105 |
4XL | ≥520 | 9.24-19.00 |